Parking Lot Closure – Smith/Jones Lot

During this time, access to the parking lot via Margaret Drive will not be allowed.  Access to the east half of the parking lot will be allowed via Hackberry beginning […]

Thermal Hot Water Outage – Smith Hall

Notes:Hot Water • Building should only see minimal impact due to HW outage • This will only impact the reheating system of the building • If outside temps were to drop low enough, […]

Thermal Cold Water Outage – Smith Hall

Notes:Chilled Water • This will impact A/C for the entire building during the week of spring break • Building impact would depend on outside temps during spring break • UA OIT to verify […]

Electrical Shutdown – Blount Living Learning Center

Notes:• Building has back-up emergency generator and will remain operational • Fire alarm system is on back-up emergency power system and will remain operational • Fire pump is on back-up emergency power system […]

Thermal “Chilled WAter” Outage – Biology Building

Notes:• Entire building will be without A/C • Building heat will not be impacted • UA HVAC to setup temporary “water cooled” A/C units in rooms 211-213 (computers/office), 228, 245-246 (fish spaces) • UA […]

Thermal “Chilled Water” Outage – Little Hall

Notes:• Entire building will be without A/C • Building heat will not be impacted • UA OIT to verify if temp. A/C is needed for data closets.  UA HVAC to verify if data […]

Electrical Shutdown – Friedman Hall

Notes:• Building does not have back-up emergency generator • Fire alarm system is on battery back-up and will remain operational • Building does not have a fire sprinkler system • UA HVAC to shutoff […]

Electrical Shutdown – Lakeside East & West Residential

Notes:• This will also impact the backup emergency power system • Fire alarm system is on battery back-up and will remain operational • Fire pump for both buildings will not be operational due […]

Electrical Shutdown – AIME Building

Notes:• Building has back-up emergency generator • Fire alarm system is on the emergency power system and will remain operational • Fire sprinkler system is operated by city water pressure and will remain […]

Electrical Shutdown – Moody Music Building

This will impact all mechanical and electrical systems of the building.  Notes: • Building has a back-up emergency generator • Fire alarm system is on the emergency generator and will remain operational […]